Conditioning The Energy Storage Solution - Koch 2.0 Series Operating Manual

Energy storage solutions
Table of Contents

Advertisement

Available languages

Available languages

5.7
Basic information
The commissioning
procedure

Conditioning the Energy storage solution

• If the Energy storage solution has been de-energised for more than 1 year, it must
be conditioned. Failure to do this may result in the Energy storage solution being
damaged when the main supply voltage is switched on.
• The date of manufacture is on the model plate (
• During conditioning, the Energy storage solution is connected to the DC link but
is not ready for use.
Conditioning
time [h]
5
4
3
2
1
Fig. 16: Conditioning time, depending on the voltage-free period
Connect the Energy storage solution to the DC link
(
Chapter 5.1, page 17).
The Energy storage solution will be conditioned (charged up).
Wait for the duration of the conditioning period which corresponds to the length
of the voltage-free period (
The application can then be enabled again.
1
2
3
Voltage-free time [years]
Fig. 16).
Operating manual Energy storage solutions
5 Commissioning
Page 9, Fig. 2).
5
4
V1.3DE/EN
29