Modbus Setup - Beko METPOINT FLM SF53 Installation And Operating Manual

Thermal flow meter
Table of Contents

Advertisement

EN

6.4. Modbus setup

The METPOINT
FLM thermal flow meter is equipped with an RS-485 interface (Modbus RTU). Before starting the sensor,
®
configure the communication parameters
Modbus ID, baud rate, parity and stop bit
to enable communication with the Modbus master.
Setup → ModBus Setup
Default (factory) settings:
Modbus ID:
1
Baud rate:
19200
Stop bit:
1
Parity:
even
Caution:
If the sensor is the last device in the Modbus system, it must be terminated. For further information, see chapter "4.5. Modbus end
termination" on Page 26.
METPOINT
SF53
®
Save the settings by pressing the "Save" button.
To apply the default (factory) settings, press the "Set to De-
fault" button.
Installation and operating manual
33