4.4.3. Galvanically isolated pulse output

Connection by means of plug-type connector B.
Connection diagram for METPOINT
Pin assignment - sensor
PIN-1
+ U
V
PIN-4
Pulse
PIN-5
Pulse
PIN-3
- U
V
PIN-2

4.5. Modbus end termination

If the METPOINT
FLM is the last device in the Modbus system, it must be terminated. The sensor has a built-in internal
®
switchable terminator. To activate this terminator, undo the top 2 threaded pins on the housing, lift off the cover and set the DIP
switch (1) to "ON". When re-closing the sensor housing, ensure that the housing gasket is correctly installed.