Connection To Metpoint ® Bdl Compact; Bidirectional Rs485 Bus System; Current Output 4 - Beko METPOINT FLM SF53 Installation And Operating Manual

Thermal flow meter
Table of Contents

Advertisement

EN
4.4. Connection to METPOINT

4.4.1. Bidirectional RS485 bus system

Connection is made using the A plug-type connector.
Connection diagram for METPOINT
q
Sensor pin assignment
PIN-1
+ U
V
PIN-3
- U
V
PIN-2
+ A
PIN-4
- B
PIN-5
4.4.2. Current output 4 ... 20 mA, 3-wire
Connection is made using the A plug-type connector.
Connection diagram for METPOINT
q
Pin assignment - sensor
PIN-1
+ U
V
PIN-3
- U
V
PIN-5
+ I
OUT
PIN-2
PIN-4
METPOINT
SF53
®
BDL compact
®
SF53 and METPOINT
®
1
+ U
V
V
3
- U
V
2
+
A
-
4
RS485
B
Function
Plus (+) connection, voltage supply
Minus (-) connection, voltage supply
Non-inverted signal (+) from RS485 interface
Inverted signal (-) from RS485 interface
not assigned
SF53 and METPOINT
®
1
+ U
V
V
3
- U
V
5
+ I
OUT
I
2
4 ... 20 mA
Function
Plus (+) connection, voltage supply
Minus (-) connection, voltage supply
Current output
not assigned
not assigned
BDL compact (digital board)
®
BROWN
BLUE
WHITE
BLACK
Wire colour
brown
blue
white
black
grey
BDL compact (analog board)
®
BROWN
BLUE
GREY
Wire colour
brown
blue
grey
white
black
Installation and operating manual
1
2
3
4
5
6
7
8
BDL compact pin
assignment
PIN-1
+ U
PIN-2
- U
PIN-7
(+) RS485 (A)
PIN-8
(-) RS485 (B)
1
2
3
4
5
6
7
8
9
BDL compact pin
assignment
PIN-1
+ U
PIN-2
- U
PIN-5
(+) I
V
V
V
V