6.8. 4 ... 20 mA
Setup → 4 - 20 mA
Setup → 4 - 20 mA → Channel 1
METPOINT
SF53
®
On this screen, you can adjust the settings for the 4 ... 20 mA analogue
output.
The following measurement data can be configured:
•
Flow = volume flow
•
Velocity
•
Temperature
•
unused = deactivate channel
This screenshot shows the available units for volume flow. Press the "<<" button
to page to the next screen.
The scaling of the 4 ... 20 mA analogue output can be set to automatic
("AutoRange = on") or manual ("AutoRange = off").
With "AutoRange = on", the sensor automatically calculates the valid measuring
range and associated reference conditions, based on the configured pipe
diameter.
Select "Scale 4mA" and "Scale 20mA" to manually configure the scaling of the
output (precondition: "AutoRange = off").
Installation and operating manual
Enter the scale for 4 mA and 20 mA,
respectively.