Modbus Setup - Beko METPOINT Installation And Operating Manual

Thermal flow meter
Table of Contents

Advertisement

EN

6.4. Modbus setup

The METPOINT
FLM thermal flow meter is equipped with a RS 485 interface (Modbus RTU). Before starting the sensor, configure
®
the communication parameters
Modbus ID, baud rate, parity and stop bit
to enable communication with the Modbus master.
Setup → ModBus Setup
Default (factory) settings:
Modbus ID:
1
Baud rate:
19200
Stop bit:
1
Parity:
even
Caution:
If the sensor is the last device in the Modbus system, it must be terminated. For details, see chapter „4.5. Modbus termination" auf
Seite 26.
33
Save the settings by pressing the "Save" button.
To apply the default (factory) settings, press the "Set to De-
fault" button.
Installation and operating manual
METPOINT
SF53
®

Advertisement

Table of Contents
loading

Table of Contents