Technical Data - Beko METPOINT FLM SF53 Installation And Operating Manual

Thermal flow meter
Table of Contents

Advertisement

Installation and operating manual

2.6. Technical data

Maximum positive operating
pressure
Measuring technique
Operating temperature
Measuring quantities
Sensor
Measuring medium
Humidity of medium
Voltage supply
Power consumption
Digital output
Analogue output
Pulse output
Accuracy
Display
Screw fitting
Material
14
Technical data
SF53
16 bar, optionally 50 bar
Calorimetric
Sensor tube and fittings: −30 ... +140 °C
Housing: −30 ... +80 °C
m³/h (factory settings)
On the display version, the following units can be chosen:
m³/min, l/min, l/s, ft/min, cfm, m/s, kg/min, kg/s
Pt45, Pt1000
Compressed air, nitrogen
max. 90% rH (non-condensing)
18 ... 36 VDC
max. 5 W
RS485 (Modbus RTU)
4 ... 20 mA (max. ohmic load < 500 Ω)
Floating switch contact
Passive: max. 48 VDC 150 mA
1 pulse per m³ or per litre
Unit adjustable at display using control keys
±1.5% of measured value
±0.3% of the final value
Display: TFT 1.8" (resolution: 220 x 167) or service LED
G½ (ISO 228/1)
Sensor tube and fittings: 1.4301 stainless steel
Housing: Powder-coated aluminium
Flange: 1.4404 (DIN EN 1092-1)
EN
METPOINT
SF53
®