Programming
Veri•Fire Programming
Using Veri•Fire with the NFS-320 or NFS2-640, click on the Point Programming icon in the Main Services column of the initial ("System
Programming") screen.
This will bring up the Point Programming Service Screen. Click on the "Prog. ACS Groups" tab. The following screen will appear.
User Map # - Choose
one that is available from
the pull-down menu.
Point - Choose a point
for programming.
Type - Choose the SLC
point type from the pull-
Mapped Device - when
all choices are made and
saved, the information
appears in this column.
Set up a user-defined group (User Map #1 is shown above) by choosing entries as indicated in the above figure for each "needed" annuncia-
tor point. "Unused" annunciator points must be mapped to a valid control point that will not be used for any other function. "Unneeded"
annunciator points require no programming; the "Mapped Device" field should be left blank.