AM2020/AFP1010 Control-By-Event

Example # 3

L1D1 activates Z1. L1M1 turns on when Z1 is active. L1D2 is a
null equation. L1M2 activates with L1D2 after a ten minute
delay. Z238 is active July 4th of every year. L1M3 will activate
when Z1 and Z238 are active. Z239 is active when Z1 is on after
a one minute delay and will stay on for 5 minutes. L1M4 turns
on when Z239 is active.
Example # 4: Fire Floor, Floor Above, Floor
Below
L1D1 activates Z1 and Z2. L1D2 activates Z1, Z2 and Z3. L1D3
activates Z2, Z3 and Z4. L1M1 will activate when Z1 is active.
L1M2 will activate when Z2 is active. L1M3 will activate when
Z3 is active. L1M4 will activate when Z4 is active.
200
L1D1
L1D2
(Z1)
( )
Z1
DEL(00.01.00 00.05.00 (Z1))
L1M1
OR(Z1)
L1M2
DEL(00.10.00 (L1D2))
L1D1
L2D1
(Z1 Z2)
Z1
Z2
L1M1
L1M2
OR(Z1)
OR(Z2)
SCS Series Manual — P/N 15712:L 7/18/16
Programming Examples
RZON
RZON
Z239
Z240
RZON
RZON
Z238
Z239
TIM( 7 - 4 - )
L1M3
AND(Z1 Z238)
L1M4
OR(Z239)
L3D1
(Z1 Z2 Z3)
(Z2 Z3 Z4)
Z3
L1M3
L1M4
OR(Z3)
OR(Z4)
Z4