Size Limitations
Examples:
1.
The following Control-By-Event takes up 13 bytes in memory:
Size in bytes
2.
The following CBE takes up 11 bytes in memory:
Size in bytes
Due to the 14-byte size limitation, it may be necessary to use more than one Equation or List to accomplish a desired result. Through the use
of reverse activating zones, an equation which normally would contain too many bytes can be broken up into several smaller equations.
In the example below, a control module is to be activated by any one of 14 software zones:
Z4
Z3
Z2
CBE Equation for L1M1:
OR( Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z11 Z12 Z13 Z14 )
1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 = 16 Bytes
SCS Series Manual — P/N 15712:L 7/18/16
OR(
Z1
Z4
Z9
1
+ 1
+ 1
+ 1
DEL(
00.00.30 00.01.30
1
+ 6
Z6
Z5
Z1
Z16
Z23
L1D3
+ 1
+ 1
+ 3
(
Z1
)
)
+1
+1
+1
+1
Z7
Z8
L1M1
AM2020/AFP1010 Control-By-Event
L2M7
)
+ 3
+ 1
= 13
=
11
Z9
Z10
Z14
(too many)
Z11
Z12
Z13
195