C.4.1: History/Printer - Honeywell NOTIFIER SCS Series Operation And Installation Manual

Smoke and hvac control station
Table of Contents

Advertisement

Special Applications
ZL498 = OR(SCSDIS(A25))
ZL499 = OR(AUTO(A25))
ZL500 = NOT(SCSDIS(A25))
ZL501 = AND(ZL499, N1ZL499)
N1ZL500
Figure C.2 Programming Example 2: Secondary Panel, Highest Priority, Normally Disabled
History/Printer
Figure C.3 shows the printer output for enable/disable switch state changes.
CLEARED ACTIVE
ACTIVE
204
NCA-2 (N2)
Secondary MSCS Panel
Programming
Figure C.3 Event History Example: Activating the Enable Switch
Custom Graphics
Annunciator
User interface for
Secondary MSCS:
SCS-8L
LDM-32
• Enable/Disable switch
(A25)
• Control switches
• Visual indicators
Visual
Indicators
Secondary SCS
ZL498 will be active when the secondary's
Disabled
enable/disable switch is disabled.
--
Required for Multiple Smoke Control Systems
applications; monitors the Auto status of the SCS-8L
(designated as A25 in this example).
Address must be lower than that of the MSCS
Control Zone.
Secondary SCS
ZL500 identifies the MSCS Control Zone of the
Active
secondary NCA-2. This logic zone will be active
when the secondary's enable/disable switch is
enabled.
--
Required to track if the SCS-8L is in Auto; must use
the next logic zone address after the MSCS Control
Zone of the secondary NCA-2.
Primary SCS
N1ZL500 identifies the MSCS Control Zone of the
Active
primary NCA-2.
MSCS CONTROL ZONE
10:10:28A WED NOV 13, 2013 ZL0500
MSCS CONTROL ZONE
10:10:24A WED NOV 13, 2013 ZL0500
Multiple Smoke Control Station
Notes
SCS Series Manual — P/N 15712:L 7/18/16