C.4: Read Status - Honeywell NOTIFIER SCS Series Operation And Installation Manual

Smoke and hvac control station
Table of Contents

Advertisement

Read Status
C.4 Read Status
The NFS2-3030 or NCA-2 can read status of the SCS-8L which is connected to it. It is accessed through the keypad of the local panel.
Figure C.4 shows the display and descriptions of the fields when a switch group is in time out trouble.
Annunciator/Point
Address
Annunciator Label
SCS Status
Switch-group Label
Switch-group Number
Toggle-switch
Annunciator Point
Designation
Annunciator Point
Annunciator/Point address. Address range to be displayed.
Annunciator label. User-programmed 40-character text label for the SCS.
SCS status. Status of the smoke control system: NORMAL; COMM LOSS; DIP SW DEFAULT; MODE CONFIG; EXPANDER
CONFIG; EXTERNAL TROUBLE.
See n"FSCS Module Trouble" on page 62 or "HVAC Module Trouble" on page 73.
Switch-group label. User-programmed 40-character text label for the switch group.
Switch-group number. Displays the switch group number.
Toggle-switch position. Configuration of the selected switch group: AUTO, ON/OPEN, OFF/CLOSED.
Annunciator point designation. List of up to four points associated with the selected switch group.
Annunciator point type. Identifies whether the designated point is a control or monitor point.
Switch-group enhanced trouble type. Status of the selected switch group: NORMAL, DEVICE MISMATCH, DEVICE TROUBLE,
DIP SW MISMATCH, TIME OUT. See "FSCS Toggle Switch Group Trouble" on page 63 or "HVAC Toggle Switch Group Trouble"
on page 74.
Point state. ON, OFF.
Point status. Status of points P01-P04 of the selected switch group.
– CON modules status: NORMAL, NO ANSWER; INVALID RESPONSE; MISMAT HDW TYPE; DISABLED.
– MON modules status: NORMAL, NO ANSWER; INVALID RESPONSE; MISMAT HDW TYPE; DISABLED;
OPEN CIRCUIT.
Figure C.5 shows the display and descriptions of the fields when the primary command node is in normal condition.
Annuciator/Point Address
Group Type
SCS Mode
Mode Type
Dipswitch Setting
Trouble Reporting Delay
Group type. For FSCS Settings, see Table 3.5. For HVAC settings, see Table 3.10
SCS mode. FSCS, HVAC.
Mode type. Title of field displays the current SCS mode.
SCS Series Manual — P/N 15712:L 7/18/16
= = = = = = = = R E A D A D D R E S S : A 2 5 P 0 1 - 0 4 = = = = = = = =
A C S B O A R D L A B E L
S T A T U S : E X T E R N A L T R O U B L E
S G L A B E L
S G 0 1 S T A T U S : A U T O
Position
P 0 1 C O N N 0 0 3 L 0 3 M 1 0 0 O F F N O R M A L
P 0 2 C O N N 0 0 3 L 0 3 M 1 0 2 O N
P 0 3 M O N N 0 0 3 L 0 3 M 1 0 1 O F F N O R M A L
P 0 4 M O N N 0 0 3 L 0 3 M 1 0 3 O F F N O R M A L
= = = = = = 0 1 : 3 8 : 4 1 P M O N N O V 1 1 , 2 0 1 3 = = = = = = =
Type
Figure C.4 Read Status Display Example 1: Switch Group in Time Out Trouble
= = = = = = = = R E A D A D D R E S S : A 2 5 P 0 1 - 0 4 = = = = = = = =
G R O U P T Y P E ( 1 - 5 ) : 0 9
M O D E ( 6 ) : F S C S
F S C S ( 7 ) : D E D I C A T E D
D I P S W I T C H S E T T I N G : x 1 1 1 1 1 1 0 / 7 E
T R O U B L E R E P O R T I N G D E L A Y : 3 0
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Figure C.5 Read Status Example 2: Primary Command Node Normal
T I M E O U T
N O R M A L
M O R E
B A C K
B A C K
Special Applications
Switch group's
Enhanced
Trouble Type
Point Address
Point State
Point Status
Binary
value
Hexadecimal
value
205