The SCS⁄SCE
The next set of equations to be determined is for the supply dampers. There are two control modules per damper, one with the capability to
close the dampers (the control module is referred to as a CON
ule is referred to as a CON
the floor that they serve. For instance, the CON
the second supply damper would be L3M7. The CON
CON
CM for the second supply damper would be L3M8 (L3M5 and L3M6 would be the monitor modules for one damper, L3M9 and
OFF⁄CL
L3M10 would be the monitor modules for the second). The two supply dampers per floor are to close when a fire is detected on that floor
and they are to open when a fire is detected on an alternate floor. However, the dampers are not to open or close in response to the manual
pull station. The CBE equation for the two CON
If a device on floor 6, with the exception of the manual pull station, becomes ACTIVE, the CBE equation for Z206 will become TRUE. As a
result, all equations that contain Z206 in them will be TRUE. When the equations become TRUE, the CON
open all the dampers except those on floor 6. The CBE equations for L6M3 and L6M7 are the only equations that will be FALSE in this case
and subsequently not open the dampers on floor 6.
The CBE equation for the CON
OR(Z20x)
where x is one of the eight reverse software zones corresponding to the appropriate floor. If a device on floor 6, with the exception of the
manual pull station, becomes active, the CBE equations for L6M4 and L6M8 would become TRUE. When the equations become TRUE the
CON
CMs are active and close the dampers.
OFF⁄CL
The next set of equations to be determined is for the exhaust dampers. Let us assume that the four control modules for the exhaust dampers
are wired on the SLC loop for the floor that they serve. For instance the two CON
the two CON
OFF⁄CL
L3M17 and L3M18 would be the monitor modules for the second). The two return dampers per floor are to open when a fire is detected on
that floor and they are to close when a fire is detected on an alternate floor. However, the dampers are not to open or close in response to the
manual pull station. The CBE equation for the two CON
OR(Z20x)
where x is one of the eight reverse software zones corresponding to the appropriate floor. If a device on floor 6, with the exception of the
manual pull station, becomes active, the CBE equations for L6M11 and L6M15 would become TRUE. When the equations become TRUE
the CON
CMs are active and open the dampers.
OFF⁄CL
The CBE equation for the CON
If a device on floor 6, with the exception of the manual pull station, becomes ACTIVE, the CBE equation for Z206 will become TRUE. As a
result, all equations that contain Z206 in them will be TRUE. When the equations become TRUE, the CON
close all the dampers except those on floor 6. The CBE equations for L6M3 and L6M7 are the only equations that will be FALSE in this case
and subsequently not close the dampers on floor 6.
102
CM). Let us assume that the four control modules for the two supply dampers are wired on the SLC loop for
ON⁄OP
ON⁄OP
ON⁄OP
module #:
L1M3 and L1M7
L2M3 and L2M7
L3M3 and L3M7
L4M3 and L4M7
L5M3 and L5M7
L6M3 and L6M7
L7M3 and L7M7
L8M3 and L8M7
CMs of each floor would be:
OFF⁄CL
CMs for floor 5 would be L5M12 and L5M16 (L3M13 and L3M14 would be the monitor modules for one damper,
CMs of each floor would be:
OFF⁄CL
module #:
L1M3 and L1M7
L2M3 and L2M7
L3M3 and L3M7
L4M3 and L4M7
L5M3 and L5M7
L6M3 and L6M7
L7M3 and L7M7
L8M3 and L8M7
Building-Specific Operation and Programming Examples
CM) and one with the capability to open the dampers (the control mod-
OFF⁄CL
CM for the first supply damper on floor 3 would be L3M3 and the CON
CM for the first supply damper on floor 3 would be L3M4 and the
OFF⁄CL
CMs of each floor would be:
CBE equation:
OR(Z202 Z203 Z204 Z205 Z206 Z207 Z208)
OR(Z201 Z203 Z204 Z205 Z206 Z207 Z208)
OR(Z201 Z202 Z204 Z205 Z206 Z207 Z208)
OR(Z201 Z202 Z203 Z205 Z206 Z207 Z208)
OR(Z201 Z202 Z203 Z204 Z206 Z207 Z208)
OR(Z201 Z202 Z203 Z204 Z205 Z207 Z208)
OR(Z201 Z202 Z203 Z204 Z205 Z206 Z208)
OR(Z201 Z202 Z203 Z204 Z205 Z206 Z207)
ON⁄OP
CMs of each floor would be:
ON⁄OP
CBE equation:
OR(Z202 Z203 Z204 Z205 Z206 Z207 Z208)
OR(Z201 Z203 Z204 Z205 Z206 Z207 Z208)
OR(Z201 Z202 Z204 Z205 Z206 Z207 Z208)
OR(Z201 Z202 Z203 Z205 Z206 Z207 Z208)
OR(Z201 Z202 Z203 Z204 Z206 Z207 Z208)
OR(Z201 Z202 Z203 Z204 Z205 Z207 Z208)
OR(Z201 Z202 Z203 Z204 Z205 Z206 Z208)
OR(Z201 Z202 Z203 Z204 Z205 Z206 Z207)
CMs become ACTIVE and
ON⁄OP
CMs for floor 5 would be L5M11 and L5M15, and
CMs become ACTIVE and
ON⁄OP
SCS Series Manual — P/N 15712:L 7/18/16
CM for
ON⁄OP