AM2020/AFP1010 Control-By-Event

NOT

Operator: The NOT operator inverts the state of the operand (activated to deactivated OR deacti-
vated to activated).
Equation: NOT(Z2)
The control module will remain activated UNTIL the operand comes into alarm.
IF Software Zone 2 is in alarm,
THEN this control module will be deactivated.

XZONE

Operator: For Cross Zone operation, the XZONE operator
is used.
Equation: XZONE(Z23)
IF ANY combination of TWO or more initiating devices
(L1D1, L1D2, L1D3, L1D4) that have been programmed
(Control-By-Event) to this software zone (Z23) come into
alarm,
THEN this control module will be activated.

DEL

Operator: For delayed operation, the DEL operator is used.
Equation: DEL(HH.MM.SS HH.MM.SS (Z1))
Example:
L1M3 activates Forward Activating Zone 223 (Z223).
L1M2 CBE is: DEL(00.00.30 00.01.30 (Z223))
IF Z223 has been active for 30 seconds
THEN L1M2 will become active. L1M2 will stay active for 1 minute and 30 seconds.
192
Duration
Delay
Equation
(optional)
L1D1
L1D2
(Z23)
(Z23 )
Internal
L1D4
(Z2)
Z2
L1M1
NOT(Z2)
L1D3
L1D4
(Z23)
Z23
L1M3
XZONE(Z23)
L1M3
Z223
L1M2
DEL(00.00.30 00.01.30 (Z223))
SCS Series Manual — P/N 15712:L 7/18/16
Operators
(Z23)
(Z223)