Building-Specific Operation and Programming Examples

4=FPRG
Option 4 from the Programming Menu allows the programmer to completely program all of the addressable detectors, modules, software-
defined zones and EIA-485 protocol points in the AM2020/AFP1010 system. The programming examples illustrate the CRT screen prompts
displayed during Full Point Programming.
After entering Full Point Programming, the display will show the following:
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@INSTALL@(BCKSPC@TO@ABORT)@@@@@@:
NOTE:
The control panel continuously loops back through the Full Point Programming routine, allowing the programmer to enter devices,
software zones or annunciator points one after the other. Use the Backspace key to exit Full Point Programming.
Example: Programming EIA-485 Protocol Points
Installation of individual annunciator points.
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@INSTALL@(BCKSPC@TO@ABORT)@@@@@:@A12P10
ENTER@TYPE@ID@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@AMON
Example: Programming Addressable Detectors
Photoelectric Smoke Detector on SLC LOOP 2 programmed to activate three software zones -Z13, Z29, and Z240 (Z240 is for FSCS Mode
operation, Version 4.0 AM2020/AFP1010 or greater) - and also mapped to annunciator module address "02" point "02".
PRESS@1=PSYS,2=FSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG,8=HIS@@@@@@@@@@@@@@@@@@:@4
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@INSTALL@(BCKSPC@TO@ABORT@@@@:@L2D23
ENTER@TYPE@ID@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@PHOT
ENTER@CONTROL-BY-EVENT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
(Z13@Z29@Z240)@
ENTER@20@CHARACTER@CUSTOM@LABEL@@@@@@@@@@@@@@@@@@@@@@@@@@@:@MAIN@LOBBY@DETECTOR@
IS@THE@DETECTOR@VERIFICATION@OPTN@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO):@Y
ENTER@THE@DETECTOR@SENSITIVITY@SELECTION@FOR@THIS@DEVICE@(L=LOW,M=MED,H=HIGH):@H
IS@THE@TRACKING@OPTION@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@@@@@@@:@Y
IS@THERE@DAY/NIGHT@SENSITIVITY@CONTROL@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@
DO@YOU@WANT@THIS@POINT@MAPPED@TO@AN@ANNUNCIATOR?@(Y=YES,N=NO)@@@@@@@@@@@
ENTER@AXXPYY@FOR@ANNUNCIATOR@POINT@MAPPING@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@A2P2
Example: Programming Control Modules
Control Module on SLC Loop 2 programmed to turn on in response to an alarm condition on either of two software zones (Z13 or Z29), and
also mapped to annunciator module address "02" point "04".
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@INSTALL@(BCKSPC@TO@ABORT)@@@@@@:@L2M19
ENTER@TYPE@ID@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@CMXS
ENTER@CONTROL-BY-EVENT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
OR(Z13@Z29)@
ENTER@20@CHARACTER@CUSTOM@LABEL@@@@@@@@@@@@@@@@@@@@@@@@@@@:@MAIN@LOBBY@BELLS
IS@THE@SIGNAL@SILENCE@OPTION@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@:@Y
IS@THE@WALK@TEST@OPTION@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@@@@@@:@N
DO@YOU@WANT@THIS@POINT@MAPPED@TO@AN@ANNUNCIATOR?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@:@Y
ENTER@AXXPYY@FOR@ANNUNCIATOR@POINT@MAPPING@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@A2P5
NOTE:
Control modules that activate monitor modules via physical connections must not have the walk test option enabled.
3.10 Building-Specific Operation and Programming Examples
The eight story building shown in Figure 3.35, originally shown in Figure 2.24, will be used to detail the procedure for smoke control using
the SCS⁄SCE. The building is eight stories, where each floor is designated as a smoke control zone. There is also a stairtower and elevator
shaft to consider. The system depicted here will utilize pressurization where all nonsmoke zones will be pressurized. The stairtower will use
a multiple injection system and the elevator hoistway will only be pressurized to prevent the migration of smoke (it will not be used for evac-
uation). We will also assume that the FACP and associated devices for fire protection are already installed. There are six smoke detectors and
one pull station on each floor. There is also one waterflow switch per floor on the sprinkler system to detect the flow of water on each floor.
Before proceeding, the designer must decide whether the system is to be a dedicated or non-dedicated system. This example will be demon-
strated both ways. The first design will use a dedicated system. For the dedicated system all fans are normally off, all supply dampers and all
exhaust dampers are normally closed (when no power is applied to the damper, it is closed). Since the system is not used for any reason other
than smoke control, the fans are off, the supply dampers are closed and the exhaust dampers are closed before a fire is detected.
SCS Series Manual — P/N 15712:L 7/18/16
The SCS⁄SCE
@@:@Y