SCS Dipswitch Settings for HVAC Mode

The tables on the pages that follow describe the dipswitch settings necessary to configure the SCS⁄SCE for many variations of heating, ven-
tilating and air conditioning control. The same dipswitch settings and switch group layouts apply when an SCS is used without an SCE. Each
description of a dipswitch setting follows the format shown below:
This diagram depicts the layout of the switch
Reference
groups and the group type associated with
Number
each switch group for the particular
dipswitch setting on the right.
19
14
5
14
14
5
14
14
5
14
14
5
14
SCS-8
SCE-8
For instance, this particular dipswitch setting allows the SCS⁄SCE to function in the HVAC mode (dipswitch 6 in the OFF position). The set-
ting for switches 1-5 not only select the HVAC group types of 14 and 5 but configure the switch group layout as shown to the left, where
switch groups 1, 2, 3, 4, 9, 10, 11, and 12 are set for group type 8 operation and switch groups 5, 6, 7, 8, 13, 14, 15, and 16 are set for group
type 1.
66
Table 3.9 HVAC Mode Switch Group Types
, VER
and VER
OFF⁄CL
ON⁄OP
OFF⁄CL
ON⁄OP
and VER
ON⁄OP
OFF⁄CL
and VER
ON⁄OP
ON⁄OP
, VER
and VER
ON⁄OP
ON⁄OP
OFF⁄CL
, CON
ON⁄OP
OFF⁄CL
, CON
and VER
ON⁄OP
OFF⁄CL
OFF⁄CL
, CON
and VER
ON⁄OP
OFF⁄CL
ON⁄OP
, CON
, VER
and
ON⁄OP
OFF⁄CL
ON⁄OP
When used with an SCE, eight switch groups are
5
available for group type 14 operation and eight are
5
available for group type 5 operation in the format
5
shown to the left. Type 14 switch groups require
control modules and monitor modules. Type 14
5
switch groups are usually only used for fans. One
control module is used for the ON control of the fan,
the other control module is used for the OFF control.
The monitor module is used for the ON verification of
the fan. Type 5 switch groups require one control
module and one monitor module. Type 5 switch
groups can be used for fans or dampers. The control
module is used for OFF control of a fan and the
monitor module is used for the OFF verification of the
fan.
Turn a fan off (close a damper) and verify when the fan is on and off (damper
open and closed)
Turn a fan on (open a damper)
Turn a fan on (open a damper) and verify when the fan is off (damper closed)
Turn a fan on (open a damper) and verify when the fan is on (damper open)
Turn a fan on (open a damper) and verify when the fan is on and off (damper
open and closed)
Turn a fan on and off (open and close a damper)
Turn a fan on and off (open and close a damper) and verify when the fan is off
(damper closed)
Turn a fan on and off (open and close a damper) and verify when the fan is on
(damper open)
Turn a fan on and off (open and close a damper) and verify when the fan is on
and off (damper open and closed)
This text describes the functions,
capabilities, and limitations of the
SCS⁄SCE for the particular dipswitch
setting.
This diagram depicts the dipswitch
setting necessary to configure the
SCS⁄SCE for the capabilities
mentioned to the left.
OFF
ON
Switches 1-5 select
the SCS⁄SCE for a
particular configuration
of switch group types
Switch 6, when in the
OFF position, selects
HVAC Mode.
See Table 3.4 for settings of
switches 7 and 8.
SCS Series Manual — P/N 15712:L 7/18/16