Switch Group Leds For Fscs Mode - Honeywell NOTIFIER SCS Series Operation And Installation Manual

Smoke and hvac control station
Table of Contents

Advertisement

The SCS⁄SCE
8
9
SWITCH
GROUP TYPE
1-9

Switch Group LEDs for FSCS Mode

FSCS Toggle Switch Group LEDs
There are three LEDs associated with each SCS⁄SCE toggle switch. These LEDs function according to Table 3.8.
SWITCH
GROUP TYPE
1
2
3
4
5
6
7
8
9
FSCS Trouble Conditions
When an SCS⁄SCE trouble condition exists, the type of trouble can be identified on the SCS⁄SCE modules by a series of one or more LED
flashes (trouble codes) as described in this section.
FSCS Module Trouble
A trouble affecting the entire SCS⁄SCE is called a module trouble condition. A module trouble may occur for any of the following reasons:
Communication is lost with the FACP/Network Annunciator. All amber trouble LEDs will flash rapidly and the piezo will sound.
During this condition, an annunciator communication fault will be displayed at the control panel. (COMM LOSS)
Example: Trouble with the EIA-485 communication loop or incorrect address selection.
Annunciator points 33-64
All yellow LEDs will flash rapidly and the piezo will sound.
For AM2020/AFP1010 only: Annunciator points 33 - 64 are not programmed as type ID ACON and an SCE is not
connected or responding to the SCS. During this condition, an expander trouble will be displayed at the control panel.
NFS-320 or NFS2-640 with NCA-2: Annunciator points 33 - 64 are not programmed to an unused output point and the
SCE-8 is not connected. During this condition, an expander trouble will be displayed at the control panel.
62
Table 3.7 FSCS Toggle Switch Functions (Alarm Condition)
Activates CON
CM
ON⁄OP
Deactivates CON
CM
OFF⁄CL
Activates CON
CM
ON⁄OP
Deactivates CON
CM
OFF⁄CL
FSCS DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON
see above
Table 3.8 FSCS Toggle Switch Group LED Operation
Green LED
turns ON when
VER
MM Deactivates
OFF⁄CL
VER
MM Activates
ON⁄OP
VER
MM Activates
ON⁄OP
VER
MM Deactivates
OFF⁄CL
VER
MM Activates
ON⁄OP
VER
MM Activates
ON⁄OP
VER
MM Deactivates
OFF⁄CL
VER
MM Activates
ON⁄OP
VER
MM Activates
ON⁄OP
depends on CBE after Reset
depends on CBE after Reset
AUTO
depends on CBE after Reset (see
Automatic Control in Dedicated
System Operation section)
Yellow LED
turns ON when
VER
MM Activates
ON⁄OP
VER
MM Deactivates
ON⁄OP
VER
MM Activates
ON⁄OP
VER
MM Activates
ON⁄OP
VER
MM Deactivates
ON⁄OP
VER
MM Activates
ON⁄OP
VER
MM Activates
ON⁄OP
VER
MM Deactivates
ON⁄OP
VER
MM Activates
ON⁄OP
Deactivates CON
ON⁄OP
Activates CON
CM
OFF⁄CL
Deactivates CON
ON⁄OP
Activates CON
CM
OFF⁄CL
OFF
see above
Amber LED
turns ON when
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
see FSCS Trouble Conditions
SCS Series Manual — P/N 15712:L 7/18/16
Configuration
CM
CM

Hide quick links: