Range adjustment
18/26
Building Technologies Division

Electronic version

4
0-135?
5
1 2 3
4
5
6
X2
X1
Adjust the range of the analog signal to match the switch positions (min. and max.
position):
1. Set cam I to the required high-fire position (e.g. 85°; position is indicated on the scale
next to the cam).
2. Set cam V to the required low-fire position (e.g. 20°).
3. Preset the signal at the analog input according to the required high-fire position
(e.g. 20 mA).
4. Turn the potentiometer for maximum angular rotation
a) clockwise, if the actuator has not yet reached its maximum angular rotation, or
b) counterclockwise until the actuator starts
5. Preset the signal at the analog input according to the low-fire position (e.g. 4 mA).
6. Turn the potentiometer for minimum angular rotation
a) counterclockwise, if the actuator has not yet reached its minimum angular
rotation, or
b) clockwise until the actuator starts
Modulation always takes place between high- and low-fire.
Also, it is possible to define a closed position or a separate ignition position by setting
cam VI (independent of cam V, e.g. for defining a position higher than the low-fire
position).
Low-voltage terminals
X1-1
2...10 V
X1-2
GND
X1-3
4...20 mA
0...135  1
X1-4
0...135  2
X1-5
0...135  3 (GND)
X1-6
Mains voltage terminals
X2-1
Opening (I)
X2-2
Move to low-fire (V)
X2-3
Position reached
X2-4
Closing/ignition (VI)
X2-5
Controller release
X2-6
Neutral
* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.
Dimensioning
Input
max. DC 10 V
to X1-2
Input
Input
Max. 20 mA to X1-2
Input
Input
Input
Dimensioning
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
Output
AC 120 V / AC 230 V
max. 10 mA, cos >0.9
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Input
AC 120 V / AC 230 V
max. 60 mA / 30 mA
Input
AC 120 V / AC 230 V
max. 60 mA / 30 mA
CC1N7817en
24.02.2015