SQM5... Reversing Actuator with Line Voltage Input Signal
Product Description
Reversing actuator used to position flow control
valves, butterfly valves, dampers, or any application
requiring rotary motion with line voltage input signal
for Position Proportioning or Floating Control.
Product Numbers
SQM5x.xxxRxAx for line voltage input signals
Actuator Torque:
SQM50.2...
90 in/lb
SQM50.3...
90 in/lb
SQM50.4...
140 in/lb
SQM53.4...
200 in/lb
SQM56.5...
310 in/lb
SQM56.6...
400 in/lb
SQM... motors allow torque on either end of the
AGA58.3 and AGA58.4 shafts.
NOTE:
For detailed information, see Technical
Instructions 155-517P25.
Caution Notation
CAUTION:
Installation
Cover Removal
Use a Phillips screwdriver to loosen the two screws
on the actuator cover corners. See Figure 1.
Lift the screws and raise the cover. See Figure 2.
Item Number 129-399, Rev. BA
Max Shaft Torque:
AGA58.1
200 in/lb
AGA58.3
220 in/lb
AGA58.4
270 in/lb
AGA58.7
400 in/lb
Equipment damage may
occur if procedures are not
followed as specified.
Installation Instructions
Figure 1.
Rotational Direction Verification
Actuator model numbers that end with "R" are
factory configured for clockwise (cw), minimum to
maximum rotation when facing the gear end of the
actuator, or counterclockwise (ccw) rotation when
facing the other end of the actuator. The gear end of
the actuator is the side opposite of the visual
position indicator
Actuator Mounting
SQM5... actuators can be mounted in any
orientation. Optional base mounting brackets are
available.
SQM5... actuators can also be face-mounted using
self-tapping screws in combination with the various
holes on the face of the actuator gear end.
Switch Adjustment
SQM5...actuators are factory-wired with Switch I
(maximum), Switch II (fully closed/economy position)
and Switch III (minimum/low-fire). The individual
switch cams I, II, and III are factory set to 90°, 0°
and 10°, respectively. See Figures 3 and 4.
Document No. 129-399
January 18, 2008
Figure 2.
Page 1 of 4

Advertisement

loading

Summary of Contents for Siemens sqm50

  • Page 1 Position Proportioning or Floating Control. Product Numbers SQM5x.xxxRxAx for line voltage input signals Actuator Torque: Max Shaft Torque: Figure 1. Figure 2. SQM50.2… 90 in/lb AGA58.1 200 in/lb Rotational Direction Verification SQM50.3… 90 in/lb AGA58.3 220 in/lb Actuator model numbers that end with “R”...
  • Page 2 Ensure that the actuator position indicating dial is adjusted between 0° and 135°. aligned with the actuator position scale. If necessary, rotate the dial in the clockwise direction. Page 2 of 4 Siemens Building Technologies, Inc.
  • Page 3 "economy position" (switch cam II) by using the toggle switch located to the left of the Actuator damage will result if power is supplied AUTO/MAN switch. to terminals A and Z simultaneously. Siemens Building Technologies, Inc. Page 3 of 4...
  • Page 4 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2008 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc.