Connection diagrams and connection terminals (cont'd)
SQM4x.x3xxxx
R
I
M
b1
a1
b2
c1
4 1
2
5
3
3 2
X2
Range adjustment
Building Technologies Division
2-position version with 2 end switches and 2 auxiliary switches, 3 relays
3
II
III
VI
a2
1
5 6
4
X1 1 2
3
X3
See SQM4x.x4xxxx in this chapter.
Mains voltage terminals
X1-1
Free
X1-2
Controller, open
X1-3
Controller release
X1-4
Auxiliary switch AUX (VI)
X1-5
Neutral
X1-6
Auxiliary switch AUX (VI)
NC opener
X2-1
Fan supply voltage
X2-2
Mains voltage, close
X2-3
Low-fire controller
X2-4
Fan motor
X2-5
Free
X3-1
Auxiliary switch AUX (VI)
NO contact
X3-2
Open (I) / close (II),
changeover relay K-C
X3-3
Operation, changeover
relay K-B
Dimensioning
---
---
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9 **
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Output
AC 120 V / AC 230 V
max. 1 A, cos >0.9 **
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Output
AC 120 V / AC 230 V
max. 1 A, cos >0.9
---
---
Output
AC 120 V / AC 230 V
max. 1 A, cos >0.9 **
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Input
AC 120 V / AC 230 V
max. 1 A, cos >0.9
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.