Β
Note:
This display is only possible in operating mode or standby!
+
+
1...3 s
+
>3 s
nfo
>1 s
Β
Note:
For meaning of the error and diagnostic codes, see chapter Error code list...
Building Technologies
15.4.2

Display of flame current ION or QRA

15.4.3

Reset

Basic Documentation LME7...
15 Operation via internal LED
+
Press
for display of the flame signal amplifier.
Signal lamp blinks green.
Display shows FL.1.
+
When pressing
(1...3 seconds), the flame signal
current is displayed.
Signal lamp blinks green.
Example: 11.
+
When pressing
(>3 seconds), the point after the
number begins to blink.
When the button is released, the value is displayed for 2
minutes.
Signal lamp blinks green.
Then, the normal display appears.
Display: Point . blinks, value 11 does not.
For reset the unit, press
When the button is released, OFF is displayed.
The basic unit is reset.
nfo
for 1...3 seconds.