Alternately
+
or
-
A
Building Technologies
15.4
Fault status messages, display of errors
15.4.1
Display of errors (faults) with lockout
Basic Documentation LME7...
15 Operation via internal LED
Display shows alternately Loc and 4.
Unit is in the lockout position.
The current error code is displayed and the signal lamp is
blinking red.
Example: Error code 4
+
-
Press
or
for display of the phase, where the fault
appeared.
Signal lamp blinks red.
Example: Phase P02
Only with modulation via analog signal
A
Press
for display of the output position / actuator
position where the error occurred.
Signal lamp lights up red.
Example: Output position / actuator position 49
92/106
CC1P7105en
17.04.2018