5.2 Setting Switches

Module No. switch
Set the module No. switch to match the number of connected modules (see Section 3.1).
Note that the following setting is prohibited:
• Setting the module No. switch to a number to which no function is assigned
(see Section 3.1).
CPL No. switch
• Set the CPL No. switch so that all the modules connected to the dual ring are assigned different
numbers. Module numbers need not be in sequence.
• Set the module No. switch and CPL. No. switch according to the number of modules
connected, as shown in Table 5-1.

Table 5-1 Setting of Module No. Switch and CPL No. Switch

Number of modules connected
33 to 64 modules
17 to 32 modules
9 to 16 modules
1 to 8 modules
Note that the following settings are prohibited:
• The module of the same CPL No. exists in the dual ring.
• The CPL No. is set to a value outside the permitted range.
When module No. switch is set to 0 or 1, an error occurs at CPL No.40 to FF.
When module No. switch is set to 2 or 3, an error occurs at CPL No.20 to FF.
When module No. switch is set to 4 or 5, an error occurs at CPL No.10 to FF.
When module No. switch is set to 6 or 7, an error occurs at CPL No.08 to FF.
CAUTION
Module No. switch
0, 1
Any value from 00 to 3F
2, 3
Any value from 00 to 1F
4, 5
Any value from 00 to 0F
6, 7
Any value from 00 to 07
CAUTION
5-3
5 OPERATION
CPL No. switch