■Wiring

Connection
Connections should only be made with the power supply turned off.
Use a separate route for the product wiring and any power or high voltage wiring. Otherwise, malfunction
may result due to noise.
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply. When a switch-mode power supply is connected to the product, switching noise will be
superimposed and the product specification can no longer be met. This can be prevented by inserting a
noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the
product or by using a series power supply instead of a switch-mode power supply.
Connecting/Disconnecting
Align the lead wire connector with the connector key groove, and insert it straight in. When the knurled part
is fully tightened. Check that the connection is not loose.
When removing the connector, unlock the knurled part and pull out the connector straight.
Connector pin numbers (lead wire)
Used as switch output device
No.
Name
1
DC(+)
2
N.C./OUT2
3
DC(-)
4
OUT1
Used as IO-Link device
No.
Name
1
L+
2
N.C./OUT2
3
L-
4
C/Q
: When using the lead wire with M8 connector included with the PFMC7 series.
Lead wire colour
Brown
12 to 24 VDC
White
Not connected/Switch output 2 (SIO)/Analogue output/External input
Blue
0 V
Black
Switch output 1
Lead wire colour
Brown
18 to 30 VDC
White
Not connected/Switch output 2 (SIO)/Analogue output/External input
Blue
0 V
Black
Communication data (IO-Link)/Switch output 1 (SIO)
Function
Function
-20-
No.PF※※-OMY0002