Mounting and Installation
■Wiring
○Wiring connections
●Connections should be made with the power supply turned off.
●Use a separate route for the product wiring and any power or high voltage wiring. Otherwise, malfunction
may result due to noise.
●If a commercially available switching power supply is used, be sure to ground the frame ground (FG)
terminal. If the switching power supply is connected for use, switching noise will be superimposed and it
will not be able to meet the product specifications. In that case, insert a noise filter such as a line noise
filter/ferrite between the switching power supplies or change the switching power supply to the series
power supply.
○Internal circuit and wiring examples
PSE54
- -
Output specification
•Used as switch output device
-N
NPN open collector 1 output
Max. 30 V, 80 mA
Residual voltage: 1.5 V or less
-P
PNP open collector 1 output
Max. 80 mA
Residual voltage: 1.5 V or less
•Used as IO-Link device
-L
-16-
No.DOC1056909-1