■[F22] Analogue output setting

This function is available when the model includes the analogue output.
Change the analogue output set value and analogue free range.
 When using a model without analogue outputs, this setting is not available and [- - -] will be displayed.
<Operation>
Press the UP or DOWN button in function selection mode to display [F22].
Setting of analogue output (voltage output only)
Press the UP or DOWN button to select 1 to 5 V output or 0 to 10 V output.
: Only 4 to 20 mA is available for current output. The display will be [4-20] and not settable.
Press the SET button to set.
Analogue free range mode setting
Press the UP or DOWN button to select the analogue free range mode.
[OFF] is selected
Press the SET button to set.
Input of set value
Press the UP or DOWN button to set the flow value that will
output 5 V (10 V) or 20 mA.
The entered flow value can be in the range: 10% of the maximum rated flow, to the
max. displayable range.
Press the SET button.
Press the SET button to set.
[F22] Setting of analogue output completed.
-57-
Move on to the setting of analogue output.
Move on to analogue free range mode setting.
[ON] is selected
Press the SET button to set.
Return to function selection mode.
No.PF※※-OMY0002