Setting Up The Zt-257X Module; Introduction Of Configurations - ICP DAS USA ZT-2570 Manual

Hide thumbs Also See for ZT-2570:
Table of Contents

Advertisement

ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ
4

Setting up the ZT-257x module

4.1 Introduction of Configurations

"Pan ID" is the group identity of a ZigBee network
1.
The identity number must be the same if they are in the same ZigBee network.
(Valid values range from 0x0000 to 0x3FFF)
"Node ID" is the identity of the ZigBee module.
2.
The identity number must be unique if it is in the same ZigBee network as
other ZigBee module. (Valid values range from 0x0001 to 0xFFF7 for a ZigBee
Router, but is fixed to 0x0000 for a ZigBee Coordinator)
"RF Channel" indicates the radio frequency channel.
3.
The value must be set to the same channel if the module is in the same ZigBee
network as other ZigBee modules.
Channel
Frequency(MHz) 2405
Use application tools or analyzers to detect the wireless signal, chose a RF
Channel which has not been occupied.
e.g. Wifi Analyzer
ICP DAS, ZT-2570/ZT-2571 User Manual, Version 1.3
Copyright @ 2013 by ICP DAS Co., Ltd. All Rights Reserved.
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru
0x00
0x01
2410
......
0x0F
......
2480