2 Troubleshooting
2.3.163 Indoor unit related error codes
Error code
Description
A0-00
Main PCB error
A1-00
EEPROM error on main PCB
A3-00
Float switch open during thermo ON in cooling mode
A6-01
Fan motor locked
A6-10
Fan motor overcurrent
A6-11
Fan motor locked
A7-00
No detection contact swing motor
A9-01
Expansion valve motor fault detection
A9-02
Expansion valve bleeding
AF-00
Float switch open during thermo OFF
AH-03
Transmission error between main PCB and
self‑cleaning PCB
AH-04
Dust detection sensor error
AH-05
Dust collection error
AH-06
Air filter rotation error
AH-07
Damper rotation error
AH-08
Filter cleaning time error
AH-09
Auto self‑cleaning disabled
AJ-01
Capacity adapter missing
AJ-02
Incorrect expansion valve motor
C1-01
Transmission error between main PCB and fan
motor PCB
C1-02
Transmission error between main PCB and auxiliary PCB
C4-02
Liquid thermistor short circuit
C4-03
Liquid thermistor open circuit
C5-02
Gas thermistor short circuit
C5-03
Gas thermistor open circuit
C6-01
Combination error: Main PCB – Fan motor PCB
C9-02
Air thermistor short circuit
C9-03
Air thermistor open circuit
CE-01
No signal from optional presence sensor
CE-02
No signal from optional floor temperature sensor
CE-03
Faulty signal from floor temperature sensor
CE-04
High temperature detection or electrical noise on
floor temperature sensor
CJ-02
Air thermistor on Remote controller short circuit
CJ-03
Air thermistor on Remote controller open circuit
U4-01
Communication error between indoor unit and
outdoor unit
U9-00
Error on other indoor unit
UA-13
Combination error: indoor unit – outdoor unit
(refrigerant)
UA-15
Outdoor unit not compatible with self‑cleaning panel
UE-00
Communication error with central controller device
Service manual
68
https://daikin-p.ru/catalog/vrv-daikn/naruzhnye-vrv-bloki-daikin
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ Heat Pump
ESIE18-14 – 2019.07