Emerson Rosemount 2088 Reference Manual page 33

Pressure transmitter
Hide thumbs Also See for Rosemount 2088:
Table of Contents

Advertisement

Reference Manual
00809-0100-4108
PV, 2V, 3V, 4V
Process Variables
Device Status
2.12.2
Choosing burst mode options in HART
Message content options:
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables and Status
Process Variables
Device Status
2.12.3
Choosing a HART
When in HART 7 mode, the following trigger modes can be selected.
Continuous (same as HART5 burst mode)
Rising
Falling
Windowed
On Change
Note
Consult your host system manufacturer for burst mode requirements.
2.12.4
Configuring burst mode using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2.12.5
Configuring burst mode using AMS Device Manager
Procedure
1. Right select on the device and select Configure.
2. Select the HART tab.
3. Enter the configuration in Burst Mode Configuration fields.
Reference Manual
®
7 trigger mode
2, 2, 5, 3
Configuration
April 2021
®
7
33