Setting pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Setting pressure units with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
Setting pressure units with a LOI
Follow
ENTER buttons to select desired unit. Save by selecting SAVE as indicated on the LCD
display screen.
Figure 2-8: Selecting Units with LOI
2.8.2
Rerange the transmitter
The range values command sets each of the lower and upper range analog values (4 and
20 mA/1–5 Vdc points) to a pressure. The lower range point represents 0 percent of range
and the upper range point represents 100 percent of range. In practice, the transmitter
range values may be changed as often as necessary to reflect changing process
requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or LOI.
Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Reference Manual
Figure 2-8
to select desired pressure and temperature units. Use the SCROLL and
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
2, 2, 1, 1, 4
UNITS
PRESS UNITS
TEMP UNITS
BACK TO MENU
EXIT MENU
Configuration
April 2021
PRESS UNITS
INH2O
MMHG
CMHG0C
MHG0C
PSI
PSF
ATM
TORR
PA
KPA
...
21