8.1.3. ROOM CO2 TRANSMITTER INSTALLATION RECOMMENDATION
If the duct CO2 transmitter is used, it must be installed in the extract air duct. To install duct transmitters, hole drilling tools
are required .
8.1.4. CO2 CONCENTRATION ACCORDING TO PETTENKOFER LIMIT
8.1.5. CONNECTION OF SUPPLY AND EXTRACT AIR DAMPERS
tuators.
Wiring diagram for RIRS VE EKO 3.0
M2, M3 – Open/Close damper actuators. Upon activation of outputs X16:17, X16:20 the dampers shall open, Upon activation of outputs X16:16,
X16:19 the dampers shall close.
Wiring diagram for RIRS VW EKO 3.0
M2 – Spring-return damper actuator. M3 – Open/Close damper actuator. Upon activation of outputs X16:17, X16:20, the dampers open, Upon
RIRS 400-700 V EKO 3.0 v2020.1
2
max. 400m
m
5 0 c
m i n .
min. 60 cm
-