Control
Parameter
Screen Name
No
GP DO1 SP
362
DEGREES
GP D01 DB
363
PERCENT
GP D01 TIME
364
DELAY
365
GP D02 MODE
GP D02 SP
366
VOLTS
367
GP D02 SP PPM
Table 12. CORE Control System Unit Parameters
Parameter Short
Description
Min.
General Purpose
D01 Set Point
-31
Degree
General Purpose
D01 Dead Band
0
Percentage
General Purpose
1
D01 Time Delay
General Purpose
0
D02 Mode
General Purpose
D02 Set Point
0
Volts
General Purpose
D02 Set Point
21
Parts Per Million
Control Value
Default
Max.
0
132
0
100
416
8160
Seconds
0
127
Selection
0
10
996
1996
70
Units
Description
General Purpose D01 Digital output
°F
control mode set point.
General Purpose D01 Digital output
control mode set point.
EXAMPLE:
If this Parameter is set
%
to 10%, then the dead-
band in Fahrenheit would
be (DO Temperature Set
Point * 10 /100).
For delay on or delay off.
GP3 Digital Out Control Mode = X + 32*Y
+ 16*Z
Input Sources X:
•
0 = None.
•
1 = Compressor 1 duty cycle.
(Compressor crankcase heater
function)
>
On when outdoor air
temperature is < = Parameter
369 and > = P 371 seconds
have passed with compressor
1 off.
>
Off when outdoor air
temperature > Parameter 369
+ 3°F (fixed dead-band) or
compressor 1 is turned on.
•
2 = On when Occupied
•
3 = On when blower on.
•
4 = On when heating demand
•
5 = On when cooling demand
•
6 = On when heating or cooling
Mode
demand
•
7 = System RH (use Parameter 368)
•
8 = System IAQ (use Parameter
367)
•
9 = System OAT (use Parameter
369)
•
10 = On based on GP3 Temperature
Sensor 1 (use Parameter 369)
•
11 = On based on GP3 Temperature
Sensor 2 (use Parameter 369)
•
12 = On based on GP3 AI1 (use
Parameter 366)
•
13 = On based on GP3 AI2 (use
Parameter 366)
•
14 = On based on GP3 AO1 (use
Parameter 366)
•
15 = On based on GP3 AO2 (use
Parameter 366)
•
Algorithm Y for Input Sources 7-15
(see 507242-01, Prodigy Application
Guide for further details).
General Purpose D02 Digital output
Volts
control mode set point.
General Purpose D02 Digital output
PPM
control mode set point.