Control
Parameter
Screen Name
No
UNOCC COOL
140
STPT
AFTERHOUR
141
OVRRD DLY
HEAT STAGE
142
DEADBAND
COOL STAGE
143
DEADBAND
COOL STAGE1
144
DIFFER
COOL STAGE2
145
DIFFER
COOL STAGE3
146
DIFFER
COOL STAGE4
147
DIFFER
HEAT STAGE1
148
DIFFER
HEAT STAGE2
149
DIFFER
HEAT STAGE3
150
DIFFER
Table 12. CORE Control System Unit Parameters
Parameter Short
Description
Min.
Unoccupied
40
Cooling Set Point
After Hours
Override Time
0
Delay
Heat Stage
1
Deadband
Cool Stage
1
Deadband
Cooling Stage 1
0
Differential
Cooling Stage 2
0
Differential
Cooling Stage 3
0
Differential
Cooling Stage 4
0
Differential
Heating Stage 1
0
Differential
Heating Stage 2
0
Differential
Heating Stage 3
0
Differential
Control Value
Default
Max.
85
95
60
480
Minutes
1
3.75
1
3.75
0.5
3
1
3
1.5
3
2
3
0.5
3
1
3
1.5
3
58
Units
Description
•
Backup unoccupied cooling set
point.
•
Used if the communications link
is lost for 5 minutes between the
CORE Unit Controller and network
°F
control panel. Used only in room
sensor applications.
•
Set point temperature must be
greater than or equal to Parameter
138 plus Parameter 152).
•
After hours override timer.
•
Only used on room sensor
applications without a network
control panel.
•
Heating dead-band. Used only with
CORE Unit Controller room sensor
applications.
°F
•
Dead band must be less than or
equal to Parameter 152 minus
Parameter 143.
•
Cooling dead-band. Used only with
room sensor applications.
°F
•
Dead band must be less than or
equal to Parameter 152 minus
Parameter 142.
•
Cooling stage 1 differential. Used
only with room sensor applications.
°F
•
Differential temperature must be
less than or equal to Parameter 145.
•
Cooling stage 2 differential. Used
only with room sensor applications.
•
Differential temperature must be
°F
greater than or equal to Parameter
144 and less than or equal to
Parameter 146.
•
Cooling stage 3 differential. Used
only with room sensor applications.
•
Differential temperature must be
°F
greater than or equal to Parameter
145 and less than or equal to
Parameter 147.
•
Cooling stage 4 differential. Used
only with room sensor applications.
°F
•
Differential temperature must be
greater than or equal to Parameter
146.
•
Heating stage 1 differential. Used
only with room sensor applications.
°F
•
Differential temperature must be
less than or equal to Parameter 149.
•
Heating stage 2 differential. Used
only with room sensor applications.
°F
•
Differential temperature must be
greater or equal to Parameter 148.
•
Heating stage 3 differential
temperature. Used only with room
sensor applications.
°F
•
Differential temperature must be
greater than or equal to Parameter
149.