16. Quick Start Guide
Check rooftop unit electrical power for proper voltage and phasing. Check gas train components.
a. Turn on unit and dismiss alarm messages as necessary.
b. Follow SETUP > INSTALL menu to properly configure unit
c. Be sure unit is in normal operating mode as seen in display (COOLING, HEATING, IDLE, etc).
d. To verify operation use SERVICE > TEST menu.
Control Mode
Menu Setup Needed
THERMOSTAT
(Factory set for 2-stage thermostat)
SETUP > NETWORK INTEGRATION > NETWORK WIZARD > NETWORK
BACnet
TYPE = BACNET MS/TP
LonTalk
SETUP > NETWORK INTEGRATION > NETWORK WIZARD > = LONTALK
Damper
SETUP > TEST & BALANCE > DAMPER
SETUP > NETWORK INTEGRATION > NETWORK WIZARD > RTU
Local Mode
STANDALONE
Dehumidifier setup will be done during the SETUP >INSTALL wizard. It's the
Dehumidifier
last part of that wizard.
Change motor torque; see
Blower
SETUP > TEST & BALANCE > BLOWER
CAUTION
88
Tips
Check LEDs for signals.
•
Setup information to be verified with
integrator.
•
Follow wiring instructions including network
termination
•
Remember to set MAC address 0-127
•
Expert level BACnet service manual available.
•
Setup information to be verified with
integrator.
•
Follow wiring instructions including network
termination
•
XIF file available. Neuron ID on sticker.
•
Expert level LonTalk service manual available.
•
Verify damper minimum positions
•
Refer to Economizer section of manual for
more detail
•
Give unit time to start-up.
•
Humidity control requires sensor or error code
7649
•
Three possible connections, LOCAL
SENSOR, NETWORK SENSOR and
REHEAT DI4.
•
Analog sensor wiring is polarity sensitive
•
Final motor CFM should be set by Test and
Balance technician
•
Blower charts are located in the unit
installation instruction.