How Does Adaptive Gain Control Work; How Long Are Settings Saved In The Thermostat If Power Fails; How Does Self-Heating Compensation Work - Siemens RDS110.R User Manual

Smart thermostat wireless
Hide thumbs Also See for RDS110.R:
Table of Contents

Advertisement

11.1.19 How does Adaptive gain control work?

11.1.20 How long are settings saved in the thermostat if power

11.1.21 How does self-heating compensation work?

11.1.22 How does the thermostat adapt start optimization of
11.1.23 How does the temperature switching differential work?
11.2 Technical specifications
11.3 Cyber security disclaimer
A6V11562455_en--_b
min/K. When the room temperature is 1 °C lower than the setpoint, thermostat will
start pre-heating the room 30 minutes earlier.
See Managing application settings [➙ 27] for more information about "Optimum
start control" and "Warm-up gradient".
With adaptive gain control, the thermostat automatically adjusts the gain to a better
PID algorithm control value based on room temperature and temperature setpoint.
The gain cannot be manually changed.
fails?
User settings on the thermostat are not affected by power failure and remain until
users change the original settings.
Self-heating compensation includes two parts: self-heating compensation for relay
and device self-heating compensation. Compensation works from the time the
device is powered on.
Self-heating compensation for relay can be affected by changes to the load current
of the relay. But the device self-heating compensation cannot be directly influenced
by user.
outside temperature?
The outside temperature is not involved with logical operation.
The temperature switching differential can be controlled by PID algorithm and "2-
position". You can check the option under "Advanced Settings"> "Optimization">
"Heating control loop".
The differential is controlled by PID algorithm based on heating request.
The differential is controlled by "2-position". The hysteresis value is 0.5 °C. When
the room temperature is 0.5 °C above the setpoint, the thermostat stops heating.
When the room temperature is 0.5 °C below the setpoint, the thermostat starts
heating.
The temperature switching differential work cannot be directly influenced by the
user.
Please refer to the
datasheet of this product
Siemens provides a portfolio of products, solutions, systems and services that
includes security functions that support the secure operation of plants, systems,
machines and networks. In the field of Building Technologies, this includes building
automation and control, fire safety, security management as well as physical
security systems.
Appendices
Technical specifications
for technical specification details.
11
57 | 59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents