control actions. The same signal is also sent to the mobile application if the
Condensation monitor function is activated in the application.
Change input signal types based on the input type you've assigned. The
following signal types are supported:
NOTICE! If you haven't configured the corresponding application, some
inputs may not be selectable.
Digital input, normally open or closed
LG-Ni1000
Pt1000 (EU)
Pt1000 (NA)
NTC 10k
0...10 V*
Set the sensor evaluation mode if an external sensor is connected to either
terminal X1 or X2. You can use either the built-in and external sensors, or the
external sensors, for controlling and monitoring. The former is selected by
default. However, if no physical external sensors are connected to any control
inputs or if the input values are invalid, only the built-in sensors are used to
provide values for the thermostat. If an external temperature or humidity sensor
is connected and can provide valid values with the built-in sensors, the
thermostat displays the average value.
If you've configured the equipment type as "Electric floor heating", choose to
activate or deactivate the floor temperature input.
Configure the output as a humidifier free-standing, a dehumidifier free-standing
or a domestic hot water boiler.
Activate or deactivate the optimum start settings for heating. Activating the
optimum start settings allows unoccupied space (a scheduled "Unoccupied"
mode is running) to be pre-heated so that you can get the scheduled
temperature setpoint at your scheduled occupied time (the thermostat enters
into "Comfort" mode).
*) If you've selected 0...10 V as the signal type, you must connect a DC 0..10 V
active sensor with the thermostat. Otherwise, the calculated value may not be
accurate.
To change extended configurations
1. On the "Advanced Settings" page, tap .
2. If prompted, enter the administrator password.
3. Tap
>
.
4. Tap "OK" to stop all the thermostat's applications. The thermostat restarts.
5. After the restart is completed, tap "I/O" > "Adapt".
6. Change the settings as desired.
Operating the thermostat on the device
Advanced settings
6
37 | 59