Functions; Temperature Control - Siemens RDG20 KN Series Basic Documentation

Room thermostats, communicating and standalone
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

4

Functions

Temperature control

4 Functions
4.1 Temperature control
General note:
Parameters
Temperature control
Display
Note
Room temperature
Concurrent display of °C
and °F
Outside temperature via
bus
28 | 186
Setting control parameters (P001 etc. mentioned throughout the document), see
Control parameters [➙ 138].
The thermostat acquires the room temperature via built-in sensor, external room
temperature sensor (LG-Ni1000 or NTC 3k), external return air temperature sensor
(LG-Ni1000 or NTC 3k) or via KNX (S-Mode or LTE-Mode), and maintains the
setpoint by delivering actuator control commands to heating equipment, cooling
equipment, or both. The following control outputs are available:
On/Off control (2-position)
Modulating PI/P control with PWM output
Modulating PI/P control with 3-position control output
Modulating PI/P control with DC 0...10 V control output
The switching differential is 1 K for heating/cooling mode (On/Off valve: P051 and
P053).
The proportional band is 2 K for heating mode and 1 K for cooling mode (DC, PWM
and 3-pos valves: P050 and P052).
The integral action time for modulating PI control is adjustable via P057 (heating)
and P058 (cooling) (factory setting: 45 minutes).
The display shows the acquired room temperature or the Comfort setpoint,
selectable via P008. The factory setting displays the current room temperature.
Configure P004 to display the room temperature or setpoint in °F or °C as needed.
When P002 = 3, switch the unit between °C and °F via operating mode button, and
the symbol is displayed as
accordingly. This function is only available from product index B or a higher
version.
When P008 = 1, the Comfort setpoint is always displayed even when the operating
mode changes.
The acquired room temperature (internal or external sensor) is available as
information on the bus.
RDG2..KN can also acquire the room temperature via KNX.
With automatic changeover or continuous heating/cooling, symbols
indicate that the system is currently in heating or cooling.
With manual changeover (P001 = 3), symbols
currently is in heating or cooling mode and symbols
system is currently in heating or cooling. Thus, the symbols are displayed even
when the thermostat operates in the neutral zone.
Concurrent display of the current room temperature setpoint or current room
temperature in °C and °F is available (P009 = 1).
The outside temperature displays on the thermostat (P009 = 2). This temperature
value has only informational character.
In LTE-Mode, the outside temperature can only be received on outside
temperature zone 31.
In S-Mode, the corresponding communication object must be bound to a KNX
sensor device.
. When the unit is changed, P004 is updated
indicate that the system
indicate that the
A6V11545892_en--_e