CHAPTER 6: SETPOINTS

S2 System Setup

S2 SYSTEM SETUP

CURRENT SENSING

VOLTAGE SENSING
POWER SYSTEM
BREAKER
USER CURVE
FLEXCURVE A
FLEXCURVE B
898765A1.cdr
Current sensing
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Figure 11: Main system setup menu
Program using
EnerVista Software
PATH:
SETPOINTS > S2 SYSTEM SETUP > CURRENT SENSING
PHASE CT PRIMARY
Range: 1 A to 6000 A
Default: 500 A
Enter the primary rating of the three-phase feeder CTs wired to the relay phase CT
terminals (see above). For correct operation, the relay CT tap must match the feeder CT
tap (5 A or 1 A).
As the phase CTs are connected in wye (star), the calculated phasor sum of the three
phase currents (Ia + Ib + Ic = Neutral Current = 3I
overcurrent. In addition, a zero-sequence (core balance) CT which senses current in all of
the circuit primary conductors, or a CT in a neutral grounding conductor may also be
used.
S2 CURRENT SENSING
PHASE CT PRIMARY
[SENS] GROUND CT PRIMARY
S2 VOLTAGE SENSING
VT CONNECTION
VT SECONDARY
VT RATIO
AUX VT INPUT
AUX VT SECONDARY
AUX VT RATIO
S2 POWER SYSTEM
NOMINAL FREQUENCY
SYSTEM ROTATION
S2 BREAKER SETUP
52a CONTACT
52b CONTACT
BKR CONNECTED
Program using
EnerVista Software
) is used as the input for the neutral
0
S2 SYSTEM SETUP
Program using
EnerVista Software
6–49