Commissioning (via operating menu)
10.5

Configuration of a level measurement

1.
Setup → Device tag
 Enter device tag.
2.
Setup → Distance unit
 Select distance unit.
3.
Setup → Tank type
 Select tank type.
4.
Setup → Tube diameter (only for "Tank type" = "Bypass/pipe")
 Enter the diameter of the stilling well or bypass.
5.
Setup → Medium group
 Specify medium group ("Water based": DC>4 or "Others": DC>1,9)
6.
Setup → Empty calibration
 Enter empty distance E (Distance from reference point R to the 0% level)
7.
Setup → Full calibration
 Enter full distance F (Distance from the 0% to the 100% level).
4)
If the measuring range covers only an upper part of the tank or silo (E << tank/silo height), it is mandatory to
enter the acutal tank or silo height into the "Setup → Advanced Setup → Level → Tank/silo height" parameter. If
there is an outlet cone, the tank or silo height should not be adjusted as usually E is not << tank/silo height in
these applications.
54
R
BD
D
E
F
L
Micropilot FMR50 FOUNDATION Fieldbus
100%
0%
A0016933
4)
.
Endress+Hauser