User-Specific Applications; Commissioning (Block-Based Operation); Block Configuration - Endress+Hauser FOUNDATION Fieldbus Micropilot FMR50 Brief Operating Instructions

Free space radar
Hide thumbs Also See for FOUNDATION Fieldbus Micropilot FMR50:
Table of Contents

Advertisement

Micropilot FMR50 FOUNDATION Fieldbus
8.
Setup → Level
 Indicates the measrued level L.
9.
Setup → Distance
 Indicates the measured distance from the reference point R to the level L.
10. Setup → Signal quality
 Indicates the quality of the evaluated level echo.
11. Setup → Mapping → Confirm distance
 Compare distance indicated on the display to real distance in order to start the
recording of an interference echo map.
12. Setup → Advanced setup →Level → Level unit
 Select level unit: %, m, mm, ft, in (Factory setting: %)
The response time of the device is preset by the Tank type parameter. An enhanced
setting is possible in the Advanced setup submenu.
10.6

User-specific applications

For details of setting the parameters of user-specific applications, see separate
documentation:
BA01120F (Operating Instructions, FMR50, FOUNDATION Fieldbus)
For the Expert submenu refer to:
GP01017F/00/EN (Description of Device Parameters, FMR5x, FOUNDATION Fieldbus)
11

Commissioning (block-based operation)

11.1

Block configuration

11.1.1
Preparatory steps
1.
Switch on the device.
2.
Note the DEVICE_ID →  41.
3.
Open the FOUNDATION Fieldbus configuration program.
4.
Load Cff and device description files into the host system or the configuration program.
Make sure you are using the right system files.
5.
Identify the device using the DEVICE_ID (see Point 2). Assign the desired tag name to
the device by means of the Pd-tag/FF_PD_TAG parameter.
11.1.2
Configuring the Resource Block
1.
Open the Resource Block.
2.
If necessary, disable the lock for device operation.
3.
If necessary, change the block name. Factory setting: RS-xxxxxxxxxxx (RB2)
Endress+Hauser
Commissioning (block-based operation)