Update A Plc Cpu Without A Programmer Present - Emerson PaCSystems VersaMax Series User Manual

Table of Contents

Advertisement

User Manual
GFK-1503F
3. If the EZ Program Store device's LED is green and the PLC's Run LED is blinking, stop
Figure 221
If the switch is already on the Stop/Off position, move it to Run then back to Stop to affirm
the change. After the mode is changed to Stop No I/O, the Run LED goes off.
Note that to change the PLC mode from Run to Stop or from Stop to Run mode when an EZ
Program Store device is attached, the PLC's Run/Stop switch must be used. If a programmer
(computer) is also connected to the PLC at the same time, the programmer cannot be used
to change the PLC mode.
4. Start the programming software and change the request timeout values as needed.
5. Connect the programmer to the PLC CPU.
6. Use the programming software to read, write, or verify the data.
When performing an update with the programmer present, the pushbutton on the EZ
Program Store device is not used.
15.2
Update a PLC CPU without a Programmer
Present
With a program, configuration, tables, Ethernet Global Data, and Advanced User
Parameters (if any) already stored in an EZ Program Store device, it can be used to update
one or more other PLC CPUs of the same type. All the data stored in the EZ Program Store
device will be updated in the PLC CPU.
To update all of the data in a VersaMax PLC CPU, follow these steps:
1. Plug the EZ Program Store device into port 2 of the VersaMax PLC CPU.
The EZ Program Store Device
This blinking indicates that the Run/Stop switch is enabled, regardless of the
configuration of the switch.
the PLC by moving the Run/Stop switch from the On/Run position to the Stop/Off
position.
Chapter 15
Jan 2020
275