Ethernet LEDs
LAN
STAT
PORT 1
LAN
STAT
PORT 1
LAN
STAT
PORT 1
Ethernet Communications
Indications
3 – 2
3 – 3
3 - 4
3 – 5
3 – 6
3 - 7
4 - 1
Waiting for Ethernet
configuration data from CPU.
Off
PORT 1: PLC CPU is controlling
Slow blink
Port 1.
green
Off
Green / flickering
Waiting for IP Address LAN:
Ethernet interface is online.
Slow blink green
Flickers during activity.
Off
STAT: IP Address has not been
configured.
PORT 1: PLC CPU is controlling
Port 1.
Waiting for IP Address LAN:
Ethernet interface is online.
Green / flickering
Flickers during activity.
Slow blink green
STAT: IP Address has not been
Amber
configured.
PORT 1: Available for Station
Manager use
Actions
unexpected SWI
interrupt
prefetch abort error
data abort error
unexpected IRQ
request
unexpected FIQ
interrupt
reserved exception
error
fatal operating system
startup or EEPROM
error
IP address has not been
configured, or has been configured
as 0.0.0.0
Chapter 13
Use the PLC programmer
to update the
configuration, then store
the configuration to the
PLC.
Power cycle the PLC.
Clear faults and press the
Restart pushbutton for less
than 5 seconds to restart
the Ethernet interface.
Use the PLC programmer
to configure a non-zero IP
address.