GFK-1503F
Parameters Description
Adapter Name Always 0.0 for CPUE05
Producer ID
Group ID
Consumer
Period
Update
Timeout
Status Word
example
Parameters Description
Ethernet Configuration
The Local Producer ID of the device sending the exchange.
Used only if the same data is consumed by more than one consuming device.
Enter the same Group ID that has been configured as the "Consumer Address"
in the producer device.
Not used. Default is 200mS.
The maximum time the Ethernet interface allows between seeing samples on
the network without reporting a refresh error status. This error status means a
first or subsequent packet of data has not arrived within the specified time. The
range is 0, or 10–3,600,000 milliseconds. The value should be at least double
the producer's producer period value. The default is 0, which disables timeout
detection.
The update timeout period should be greater than the exchange production
period. (A value at least twice the production period is recommended.)
Round this value to the nearest 10 milliseconds before you enter it. The update
timeout has a resolution of 10 milliseconds. If you enter a value such as 22
milliseconds, the actual update timeout will be rounded up to 30 milliseconds.
A data range that identifies the memory location where the status value for the
consumed exchange will be placed. See chapter 13 Ethernet Communications
for details of the status value. Note that the Status Word address must be
unique; it is not automatically assigned the next highest address.
Offset
Reference Low
Status
%R
Description
High
Point
Point
99
99
Status: Where the PLC
will place the status
data.
Chapter 6
Jan 2020
65