Stainless Steel Vent Connection - RBI Infinite Energy2 IW199 Installation And Operation Instructions Manual

Table of Contents

Advertisement

11 - INSTALLATION - CATEGORY IV: Vent and combustion air
CAUTION!!!
Apply a liberal
even coat of MOMENTIVE -
RTV 106 high temperature
silicone (or equivalent) to the
internal side of the appliance
adapter (item "B" and "P"
fig.11-11)
Flue
exhaust
Combustion
air intake
N
N
R
R
A
A
F
F
P
P
Figure 11-11 - Stainless steel
air intake/vent connection
11.7.2 - Stainless steel
vent connection
Vent connection (Figure 11-
11 item "C")
a passageway for conveying
combustion gases to the outside. Vent
piping must be supported per the
National Building Code, Section 305,
Table 305.4 or as local codes dictate.
To connect a stainless steel pipe
to the vent connection proceed as
follows while referring to Figure 11-11:
1.- Dry fit adapter "R" to ensure proper
fit up before assembling adapter to
the appliance connection "B". The
adapter "R" should go completely
into the appliance adapter to ensure
proper sealing after sealant is
applied;
a. Handle adapters "R" and
020010.01.039
appliance connection "B" carefully
to prevent contamination of
surfaces;
G
G
A = MOMENTIVE - RTV 106
high temperature silicone (or
H
H
equivalent) (Field provided)
L
L
B = Flue exhaust connection
F = Mechanically secure clamp
R
R
G = Stainless steel exhaust pipe
A
A
(Field provided)
H = Combustion analization
F
F
probe (Field installed)
B
B
L = Cap (Field provided)
N = Stainless steel air inlet pipe
020010.01.038
(Field provided)
P = Air intake connection
R = Stainless steel adapter
(Field provided)
is used to provide
66
b. Apply a liberal even coat of
MOMENTIVE - RTV 106
high temperature silicone (or
equivalent) to the adapter "R"
approximately 2" beyond the
socket depth;
c. While the MOMENTIVE - RTV
106 high temperature silicone is
still wet, insert the adapter "R"
into the appliance connection "B".
NOTICE! If voids are present,
sufficient MOMENTIVE - RTV 106
was not applied and joint could be
defective;
d. Tight the clamp to mechanically
secure the joint.
2.- Insert vent pipe "G", into adapter
"R", following instruction of
stainless steel pipe manufacturer.
Extend the
flue exhaust
Extend the
pipe to
air intake
outside
pipe to
building
outside
building
Figure 11-12 - Stainless steel
air intake/vent connection
correctly in place
020010.01.016