15 - USE
15.10 - "Users'
menu"
Pressing RESET key for 2 seconds,
you will enter the "Users' menu".
When entering the "Users' menu", the
display, item "M" in Figure 15-1, will
Parameter
Parameter's description
1001
Burner 1 supply temperature
1002
Indirect water heater temperature (N/A)
1004
Outdoor sensor temperature (N/A)
1006
Burner 1 Flue gas temperature
1007
Burner 1 Return temperature
1008
Burner 1 Ionisation current
1009
State of the Local pump
1010
State of the CH pump (N/A)
1011
State of the DHW pump (N/A)
1012
Calculated CH setpoint (when 0-10Vdc input is enabled) (only for 199 model; for 399, 500, 750
and 1000 models see Parameter 1107)
1040
Burner 1 Actual Fan speed
1041
Burner 1 Ignition fan speed
1042
Burner 1 Low power fan speed
1043
Burner 1 High power fan speed
1051
Burner 1 Last lockout number
1052
Burner 1 Last Blocking error
1053
Burner 1 Number of flame failures
1055
Burner 1 Number of failed ignitions
1056
Burner 1 Total hours of operation
1057
Burner 1 Total hours of operation of the indirect water heater (N/A)
1059
**Burner 1 Interval between Lockouts. May be: 1:MIN; 2:HRS; 3:DAY; 4:WK
1060
**Burner 1 Interval between Blocking errors. May be: 1:MIN; 2:HRS; 3:DAY; 4:WK
1062
Burner 1 Water flow
1101
MULTIBURNER: number of burners ON
1102
MULTIBURNER: header temperature
1103
MULTIBURNER: any Burner into Lockout
1104
MULTIBURNER: any Burner into Blocking Error
1106
MULTIBURNER: system is in emergency mode
1107
MULTIBURNER: current multiburner setpoint
1120
MULTIBURNER: burner 1 modulating level
1121
MULTIBURNER: burner 2 modulating level
1122
MULTIBURNER: burner 3 modulating level
1123
MULTIBURNER: burner 4 modulating level
** How to read the timer values:
Eg: If it shows 1:29, it means 29 minutes;
Eg: If it shows 2:12, it means 12 hours;
Eg: If it shows 3:15, it means 15 days;
Eg: If it shows 4:26, it means 26 weeks;
start showing parameters from 1000.
Press keys
and
scroll all parameters inside this menu.
All parameters into this "Users' menu"
are reading only.
For unit models 399 up to 1000,
parameters addressed to "Burner
95
1 (Master)" are applicable for that
burner only. If you want to see the
to
same parameters for other burners
you have to connect the display to
the burner you want to see. To do this
follow procedure in Section 16.7.
Units
°F
°F
°F
°F
°F
μA (micro ampere)
ON/OFF
ON/OFF
ON/OFF
°F
rpm/min
rpm/min
rpm/min
rpm/min
\
\
no
no
Hr x 10
Hr x 10
GPM
n
°F
/
/
/
°F
%
%
%
%