13 - INSTALLATION - Gas supply
13.2 - Pipe sizing
for natural gas
Refer to Figure 13-2 for pipe length
and diameter. For additional gas
pipe sizing information, refer to ANSI
Z223.1 (or B149.1 for Canadian
installations).
Natural gas supply pressure
requirements
1.- Pressure required at the gas valve
inlet pressure port:
• Maximum 13"W.C. with no flow
(lockup) or with appliance off.
• Minimum 3"W.C. with gas flowing
(verify during high fire).
2.- Install 100% lockup gas pressure
regulator in supply line if inlet
pressure can exceed 13"W.C. at
any time. Adjust lockup regulator
for 13"W.C. maximum.
Nominal:
3/4
Actual ID:
0.824
Length (ft)
10
273
20
188
30
151
40
N/A
50
N/A
60
N/A
70
N/A
80
N/A
90
N/A
100
N/A
125
N/A
150
N/A
175
N/A
200
N/A
250
N/A
NOTICE! Maximum pipe capacity is based on a 0.60 specific gravity gas at a pressure of 0.5 PSIG and a
0.3"WC pressure drop
Figure 13-2 - Gas pipe capacity for natural gas

13.3 - Propane Gas

WARNING!!!
appliances are typically
shipped ready to fire on natural
gas. Check appliance rating
plate to determine which fuel
the appliance is set for. If
set to natural gas, it may be
converted to LP by following
instruction on Section 13.6 or
13.7. Failure to comply could
result in severe personal injury,
death, or substantial property
damage.
Pipe sizing for propane gas
Contact gas supplier to size pipes,
tanks, and 100% lockup gas pressure
regulator.
1
1 1/4
1.049
1.380
Capacity in Cubic Feet of Gas per Hour
514
1060
353
726
284
583
243
499
215
442
195
400
179
368
167
343
157
322
148
304
131
269
119
244
N/A
224
N/A
209
N/A
185
These
Iron Pipe size (in)
1 1/2
2
1.610
2.067
1580
3050
1090
2090
873
1680
747
1440
662
1280
600
1160
552
1060
514
989
482
928
455
877
403
777
366
704
336
648
313
602
277
534
83
Propane supply pressure
requirements:
1.- Adjust propane supply regulator
provided by the gas supplier for
13"W.C. maximum pressure;
2.- Pressure required at gas valve
inlet pressure port:
• Maximum 13"W.C. with no flow
(lockup) or with appliance off.
• Minimum 3"W.C. with gas flowing
(verify during high fire).
WARNING!!!
Ensure that
the high gas pressure regulator
is at least 6 - 10 ft upstream
of the appliance. Failure to
comply could result in severe
personal injury, death, or
substantial property damage.
2 1/2
3
2.469
3.068
4860
8580
3340
5900
2680
4740
2290
4050
2030
3590
1840
3260
1690
3000
1580
2790
1480
2610
1400
2470
1240
2190
1120
1980
1030
1820
960
1700
851
1500
4
4.026
17500
12000
9660
8270
7330
6640
6110
5680
5330
5040
4460
4050
3720
3460
3070