16 - MAINTENANCE

16.1 - Care and
maintenance
This section must be brought to the
attention of the user by the installer so
that the user can make the necessary
arrangements with a qualified service
agency for the periodic care and
maintenance of the appliance. User
must check its appliance follow Figure
16-1 column "User maintenance".
The installer must also inform the
user that the lack of proper care and
maintenance of this appliance and any
fuel burning equipment may result in an
hazardous condition.
Service Technician
Annual Startup:
- Address reported problems (Follow Section 16.1.1);
- Check all piping for gas leaks (Follow Section 16.1.2);
- Verify flue and air lines in good condition and sealed tight
(Follow Section 16.1.3);
- Check system water pressure/system piping/expansion tank
(Follow Section 16.1.4);
- Check control settings (Follow Section 16.1.5);
- Check ignition and flame sense electrodes (Follow Section
16.1.6);
- Check wiring and connections (Follow Section 16.1.7);
- Perform start up checkout and performance verification
(Follow Section 16.1.8);
- Flame inspection (Follow Section 16.1.9);
- Check flame signal (Follow Section 16.1.10);
- Inspect combustion chamber. Clean and vacuum if ther'is
presence of debris and/or products of the combustion
(Follow Section 16.3);
- Inspect thermal insulations inside the combustion chamber
and replace them if they are cracked or damaged (Follow
Section 16.3.1);
- Clean condensate box and fill with fresh water (Follow
Section 16.6);
- Clean air filter (Follow Section 16.5);
- Check the capacity input (Follow Section 14.9);
- Check relief valve (Follow Section 16.1.11).
Every two years:
- Suggested to replace the water flow sensor's o-rings (Follow
Section 16.11).
Figure 16-1 -
Service and Maintenance Schedules
Installer should discuss contents of
Section 15 (User's Section) with the
user.
A trained and qualified service
technician should perform the inspection
listed in these instructions before each
heating season and at regular intervals.
Service and maintenance schedules
User maintenance
Daily:
- Check appliance area (Follow Section 16.1.12);
- Check pressure gauge (Follow Section 16.1.13);
Monthly:
- Check vent piping and vent termination screen (Follow
Section 16.1.14);
- Check air piping and air termination screen (Follow Section
16.1.15);
- Check condensate drain system (Follow Section 16.1.16);
- Check any air vents on the system that no leaks are present;
Periodically:
- Test low water cut-off (if used) (Follow Section 16.1.19);
- Reset low water cut-off button (if used) (Follow Section
16.1.20);
Every six month:
- Check appliance piping (gas and water) for leaks (Follow
Section 16.1.17);
End of season months:
- Shut appliance down (unless appliance used for domestic hot
water) (Follow Section 16.1.18);
102
WARNING!!!
Servicing,
inspection and adjustment
must be done by a trained
technician in accordance with
all applicable local and national
codes. Improper servicing or
adjustment could damage the
appliance! Failure to comply
with this warning can result
in a fire or explosion causing
property damage, personal
injury or loss of life!