16 - MAINTENANCE
16.8 - How to move
a control board
Multi-burner unit models 399 to
1000 are configured to be driven by
one control board (named Burner 1
(Master)). On this board all external
devices are connected, such as: room
thermostat, outdoor sensor, pumps
commands, LWCO, and some internal
safety devices such as: blocked
drain magnetic switch, flue blocked
pressure switch, etc.
If Burner 1 control board fails, the
complete unit stops working. If the
installer doesn't have a replacement
part, it can replace Burner 1 control
board for another installed on the unit
and reactivate it.
To do so, operate as follows:
1.- Turn off the electrical power;
2.- Follow the steps in Section 16.2 to
remove the cover and gain access
to the internal components;
3.- Disconnect plug "B" (plug coming
from display) from plug "A" (plug
coming from "Burner 1 (Master)");
4.- Disconnect all other plugs from
Burner 1 (Master) control board;
SWITCH S4
A
Figure 16-13 - Control board "A"
5.- Remove the Burner 1
(Master) control board from
the appliance;
6.- Following step 3 to 5 above
to remove the board located in
the lower side of the unit;
7.- Install this last control board
in the site where there where
the Burner 1 (Master) control
board;
8.- Reconnect all plugs to this
board;
9.- Move "Switch S4" as per
Figure 16-13, from OFF
position to ON position;
10.- Pay attention that all
connections of the board
removed are not in short circuit
or in a dangerous position;
11.- Electrically insulate each one
of these plugs;
12.- Close the external jacket of
the unit;
13.- Turn the electrical power on
to the unit;
OFF position
ON position
020009.01.010_a
113
14.- Gain access to the Factory menu,
by following Section 20 and set all
parameters by following column
"Burner 1 (Master)" (pay attention
to parameter 3050. Because you
are moving a board to the master,
the 3050 value must be reduced by
one unit);
15.- Shut off electrical power to the
unit;
16.- Turn on the power to the unit.
Now the new Burner 1 control
board should drive the unit
correctly.
NOTICE! If your appliance serial
number begins with a number lower
than 160 and there is an argus vision
cascade manager connected and the
main board is not the board being
replaced please continue.
If the main board is the one being
replaced please call factory for
instructions