Local Diagnostics And Status Indicators - Bosch rexroth Automax 100 Operating Instructions Manual

Table of Contents

Advertisement

Local diagnostics and status indicators

Des.
Color
Meaning
U
Green
U
L
Logics
NET
Green/
Network status
yellow/
red
CO
Yellow/
Configuration
red
PP
Yellow
Plug-and-play
mode
RDY
Green/
Ready
yellow/
red
About this product | Automax 100 | Extension module TS-AC E2-M3-1X
Local diagnostics and status indicators
Local diagnostics and status indicators
Status
Description
On
Feed-in of logics voltage available.
Off
Feed-in of logics voltage not available.
Green ON
At least one connection to device established.
Green,
Connection to device can be established.
flashing
Yellow ON
IP configuration (IP address) is invalid (0.0.0.0).
Yellow,
BootP requests or DHCP requests/discover are sent.
flashing
Red ON
Network error, the process data watchdog was set active, the substitute
value behavior of outputs is executed.
Red, flashing
IP address conflict at static configuration via rotary coding switch (IP address
assigned twice).
Off
Device not ready for operation.
Yellow ON
Parameterization of I/O modules has failed.
Red ON
Current configuration of local bus does not correspond to saved one.
Off
Current configuration of local bus does correspond to saved one.
On
Plug-and-play mode activated.
Off
Plug-and-play mode deactivated.
Green ON
Device ready for operation.
Green/yellow,
Undervoltage or overvoltage of logics supply
flashing
Overtemperature
Yellow ON
Firmware/bus coupler booting
Yellow,
Firmware update is performed.
flashing
Bosch Rexroth AG | 05.2021 | DOK-SUPPL*-TS-AC E2-M3-ITRS-EN-P