Configuration For 480V 4-Wire Wye Synchro/Power Control Connection - GE PACSystems RX3i User Manual

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

3

Configuration for 480V 4-Wire WYE Synchro/Power Control Connection

Grid 1 Tab
Grid 2 Tab
3-44
The following shows a typical hardware configuration for a 3-phase, 4-wire WYE power
paralleling/synchronizing application. The offset and gain values are shown at their default
values. For maximum accuracy, the offset and gain values must be set, based on the
IC694PSM001 module faceplate label and on the IC694ACC200 terminal assembly label
calibration constants. Choose the 600V range and enter 480.0V as the nominal voltage.
The Nominal Voltage is the anticipated Phase-to-Neutral voltage in the WYE
configuration.
PACSystems* RX3i Power Sync and Measurement System – February 2013
GFK-2749

Advertisement

Table of Contents
loading

Table of Contents